How to Install a New HVAC Condenser Unit

Published: Dec 3, 2009
Updated: Nov 20, 2021
3 minute read

Things You Will Need

  • Copper tubing
  • Copper fittings
  • Copper tubing cutter
  • Copper straps
  • Brazing torch
  • 85/15 brazing rod
  • Tape measure
  • Cordless drill
  • Assorted wrenches
  • Utility knife
  • Nitrogen tank and hoses
  • Refrigerant gauges
  • Vacuum pump
  • Refrigerant
  • Electrical wire
  • Wire nuts
  • Electrical fittings
  • Wire stripper

You need a special refrigerant certification to handle and install the refrigerant that goes into condenser units. If you have this certification, however, you can install an HVAC condenser unit yourself.

  1. Select an appropriate location for your HVAC condenser unit. Look for a spot that is strong enough to support the unit and allows the unit to be serviced easily. Level the unit and place on treated lumber or steel framing. Anchor the unit down to prevent the unit from shifting during operation.

  2. Inspect the unit and ensure no components have come loose during shipment. Check all bolts, electrical connections, etc.

  3. Properly size all copper tubing using a line chart. Install and braze the copper tubing for the liquid and suction lines. When brazing, flow an inert gas like nitrogen through the lines to prevent scale and oxidation in the lines. The copper tubing will hook up from the condensing unit outside to the evaporator coil on the indoor unit. Secure and support all lines with copper pipe straps. The smaller the pipe, the more straps you will need.

  4. Leak-check the unit by opening all service valves and pressuring the unit to 150 PSI with dry nitrogen. Let the unit sit for several hours. If you notice the pressure has dropped, leak-test all connections and joints with soap bubbles.

  5. Insulate all copper tubing with Armaflex pipe insulation (see Reference 2). If lines are not insulated, this will cause possible unit malfunction and sweating of the copper lines. This insulation cuts very easily with a utility knife and self-adheres together.

  6. Release the nitrogen pressure out of the lines and start evacuating the lines. This is done by hooking the refrigerant gauges up to the high and low side and starting the vacuum pump. This removes all contaminants out of the lines by essentially pulling all air and moisture out.

  7. Wire the unit up to the electrical panel by consulting the individual unit's wiring diagram and local electrical codes.

  8. Charge with refrigerant. Different units use different types of refrigerant, so ensure you are using the right type by consulting the installation manual that came with your unit. Each installation manual will have a chart with how much refrigerant to put in, which depends on unit size and length of copper tubing.

  9. Hook up refrigerant gauges and amperage meter. Set the room thermostat to the desired setting and turn the power on to the unit. Observe high and low side pressures as well as temperatures. Verify these are in the operational range as determined by the installation manual. If not, add or remove refrigerant as necessary to achieve the correct readings.

Elizabeth Knoll

Elizabeth Knoll has been writing full-time since 2008. She has a deep love for gardening and has spent a vast amount of time researching that subject. Her work appears on various websites. Knoll received a certificate in Early Childhood…

Sponsored
HomeSteady Logo

HomeSteady is the ultimate guide for all your household needs, from cleaning and HVAC to electrical, DIY and maintenance.

Property of TechnologyAdvice. © 2026 TechnologyAdvice. All Rights Reserved

Advertiser Disclosure: Some of the products that appear on this site are from companies from which TechnologyAdvice receives compensation. This compensation may impact how and where products appear on this site including, for example, the order in which they appear. TechnologyAdvice does not include all companies or all types of products available in the marketplace.